CALIFORNIA ENERGY COMMISSION
JUNE 2001 500-01-020
CONSULTANT REPORTGray Davis, Governor
Prepared for:
California Energy Commission Energy Technology Development Division 1516 Ninth Street Sacramento, California 95814
Prepared by:
with
The California Energy Commission is providing this guide as an information resource to those installing photovoltaic (PV) systems under the Emerging Renewables Buydown Program. This is the first published draft of this guide and represents the current state-of-the-art in PV system installation. Revisions will be made to the document as necessary to address suggestions made by users of the guide. If anyone has suggestions on how to make this guide more useful, please do not hesitate to send those suggestions to the California Energy Commission. We hope that this guide is a worthwhile addition to the resources available for installers and look forward to your constructive comments for continued improvements.
SECTION 1: INTRODUCTION............................................................................................ 4
1.1. Basic Principles to Follow When Designing a Quality PV System.........................................4
1.2. Basic Steps to Follow When Installing a PV System...............................................................4SECTION 2: SYSTEM DESIGN CONSIDERATIONS ........................................................ 5
2.1 Typical System Designs and Options.........................................................................................5
2.1.1. Grid-Interactive Only (No Battery Backup)..........................................................................5
2.1.2. Grid-Interactive With Battery Backup..................................................................................5
2.2. Mounting Options ........................................................................................................................6
2.2.1. Roof mount..........................................................................................................................6
2.2.2. Shade Structure..................................................................................................................7
2.2.3. Building-Integrated PV Array (BIPV)...................................................................................7
2.3 Estimating System Output...........................................................................................................8
2.3.1. Factors Affecting Output .....................................................................................................8
2.3.2. Estimating System Energy Output......................................................................................9
2.4. Installation Labor Effort ............................................................................................................10
2.5. Incentives to Reduce Costs......................................................................................................10
2.6. Estimating Electrical Energy Savings .....................................................................................10
2.7. Supplier and System Qualifications ........................................................................................10
2.7.1. Pre-Engineered Systems..................................................................................................10
2.7.2. Warranties.........................................................................................................................11
2.7.3. Company Reputation (years in business, previous projects)............................................11
2.8. Overall Project Coordination ....................................................................................................12
2.8.1. Utility Considerations ........................................................................................................12
2.8.2. Acceptance of Systems (performance evaluation)...........................................................12
2.8.3. System Documentation.....................................................................................................12
2.8.4. System Monitoring ............................................................................................................12
2.9. References..................................................................................................................................13SECTION 3: SYSTEM INSTALLATION ........................................................................... 14
3.1. General Recommendations ......................................................................................................14
3.1.1. Materials recommendations..............................................................................................14
3.1.2. Equipment recommendations and installation methods...................................................14
3.2. PV System Design And Installation .........................................................................................14
3.2.1. Preparation Phase ............................................................................................................14
3.2.2. Design Phase....................................................................................................................15
3.2.3. Installation Phase..............................................................................................................16
3.2.4. Maintenance and Operation Phase ..................................................................................19
SECTION 4: SOLAR ELECTRIC (PV) SYSTEM INSTALLATION CHECKLIST ............. 20APPENDIX........................................................................................................................25
SECTION 1: INTRODUCTION
Photovoltaic (PV) power systems convert sunlight directly into electricity. A residential PV power system enables a homeowner to generate some or all of their daily electrical energy demand on their own roof, exchanging daytime excess power for future energy needs (i.e. nighttime usage). The house remains connected to the electric utility at all times, so any power needed above what the solar system can produce is simply drawn from the utility. PV systems can also include battery backup or uninterruptible power supply (UPS) capability to operate selected circuits in the residence for hours or days during a utility outage.
The purpose of this document is to provide tools and guidelines for the installer to help ensure that residential photovoltaic power systems are properly specified and installed, resulting in a system that operates to its design potential. This document sets out key criteria that describe a quality system, and key design and installation considerations that should be met to achieve this goal. This document deals with systems located on residences that are connected to utility power, and does not address the special issues of homes that are remote from utility power.
In this early stage of marketing solar electric power systems to the residential market, it is advisable for an installer to work with well established firms that have complete, pre-engineered packaged solutions that accommodate variations in models, rather than custom designing custom systems. Once a system design has been chosen, attention to installation detail is critically important. Recent studies have found that 10-20% of new PV installations have serious installation problems that will result in significantly decreased performance. In many of these cases, the performance shortfalls could have been eliminated with proper attention to the details of the installation.
SECTION 2: SYSTEM DESIGN CONSIDERATIONS
PV Electrical System Types
There are two general types of electrical designs for PV power systems for homes; systems that interact with the utility power grid and have no battery backup capability; and systems that interact and include battery backup as well.
This type of system only operates when the utility is available. Since utility outages are rare, this system will normally provide the greatest amount of bill savings to the customer per dollar of investment. However, in the event of an outage, the system is designed to shut down until utility power is restored.
Typical System Components:
PV Array: A PV Array is made up of PV modules, which are environmentally-sealed collections of PV Cells— the devices that convert sunlight to electricity. The most common PV module that is 5-to-25 square feet in size and weighs about 3-4 lbs./ft2. Often sets of four or more smaller modules are framed or attached together by struts in what is called a panel. This panel is typically around 20-35 square feet in area for ease of handling on a roof. This allows some assembly and wiring functions to be done on the ground if called for by the installation instructions.
balance of system equipment (BOS): BOS includes mounting systems and wiring systems used to integrate the solar modules into the structural and electrical systems of the home. The wiring systems include disconnects for the dc and ac sides of the inverter, ground-fault protection, and overcurrent protection for the solar modules. Most systems include a combiner board of some kind since most modules require fusing for each module source circuit. Some inverters include this fusing and combining function within the inverter enclosure.
dc-ac inverter: This is the device that takes the dc power from the PV array and converts it into standard ac power used by the house appliances.
metering: This includes meters to provide indication of system performance. Some meters can indicate home energy usage.
other components: utility switch (depending on local utility)

This type of system incorporates energy storage in the form of a battery to keep “critical load” circuits in the house operating during a utility outage. When an outage occurs the unit disconnects from the utility and powers specific circuits in the home. These critical load circuits are wired from a subpanel that is separate from the rest of the electrical circuits. If the outage occurs during daylight hours, the PV array is able to assist the battery in supplying the house loads. If the outage occurs at night, the battery supplies the load. The amount of time critical loads can operate depends on the amount of power they consume and the energy stored in the battery system. A typical backup battery system may provide about 8kWh of energy storage at an 8-hour discharge rate, which means that the battery will operate a 1-kW load for 8 hours. A 1-kW load is the average usage for a home when not running an air conditioner.
Typical System Components:
In addition to components listed in 2.1.1., a battery backup system may include some or all of the following:

BatterySystem
There are several ways to install a PV array at a residence. Most PV systems produce 5-to-10 Watts per square foot of array area. This is based on a variety of different technologies and the varying efficiency of different PV products. A typical 2kW PV system will need 200-400 square feet of unobstructed area to site the system. Consideration should also be given for access to the system. This access space can add up to 20% of needed area to the mounting area required.
2.2.1. Roof mount Often the most convenient and appropriate place to put the PV array is on the roof of the building. The PV array may be mounted above and parallel to the roof surface with a standoff of several inches for cooling purposes. Sometimes, such as with flat roofs, a separate structure with a more optimal tilt angle is mounted on the roof.
Proper roof mounting can be labor intensive. Particular attention must be paid to the roof structure and the weather sealing of roof penetrations. It is typical to have one support bracket for every 100 Watts of PV modules. For new construction, support brackets are usually mounted after the roof decking is applied and before the roofing materials is installed. The crew in charge of laying out the array mounting system normally installs the brackets. The roofing contractor can then flash around the brackets as they install the roof. A simple installation detail and a sample of the support bracket is often all that is needed for a roofing contractor to estimate the flashing cost.
Masonry roofs are often structurally designed near the limit of their weight-bearing capacity. In this case, the roof structure must either be enhanced to handle the additional weight of the PV system or the masonry roof transitioned to composition shingles in the area where the PV array is to be mounted. By transitioning to a lighter roofing product, there is no need to reinforce the roof structure since the combined weight of composite shingles and PV array is usually less than the displaced masonry product.
2.2.2. Shade Structure An alternative to roof mounting is to mount the system as a shade structure. A shade structure may be a patio cover or deck shade trellis where the PV array becomes the shade. These shade systems can support small to large PV systems.
The construction cost with a PV system is a little different than for a standard patio cover, especially if the PV array isacts as part or the entire shade roof. If the PV array ismounted at a steeper angle than a typical shade structure, additional structural enhancements may be necessary to handle the additional wind loads. The weight of the PV arrayis 3-to-5 lbs./ft2, which is well within structural limits of mostshade support structures. The avoided cost of installing roofbrackets and the associated labor could be counted towardthe cost of a fully constructed patio cover. The overall cost ofthis option will likely be higher than roof mounting, but the value of the shade often offsets the additional costs. Otherissues to consider include
Another type of system displaces some of the conventional roofing product with building-integrated PV modules. Commercially available products currently include roof slates (similar to masonry roofing) and standing seam metal roofing products. Special attention must be paid to ensure that these products are installed properly and carry the necessary fire ratings.
Dimensional tolerances are critical and installation requirements must followed precisely to avoid roof leaks.2.3 Estimating System Output
PV systems produce power in proportion to the intensity of sunlight striking the solar array surface. The intensity of light on a surface varies throughout a day, as well as day to day, so the actual output of a solar power system can vary substantial. There are other factors that affect the output of a solar power system. These factors need to be understood so that the customer has realistic expectations of overall system output and economic benefits under variable weather conditions over time.
2.3.1. Factors Affecting Output
Standard Test Conditions Solar modules produce dc electricity. The dc output of solar modules is rated by manufacturers under Standard Test Conditions (STC). These conditions are easily recreated in a factory, and allow for consistent comparisons of products, but need to be modified to estimate output under common outdoor operating conditions. STC conditions are: solar cell temperature = 25 oC; solar irradiance (intensity) = 1000 W/m2 (often referred to as peak sunlight intensity, comparable to clear summer noon time intensity); and solar spectrum as filtered by passing through 1.5 thickness of atmosphere (ASTM Standard Spectrum). A manufacturer may rate a particular solar module output at 100 Watts of power under STC, and call the product a “100-watt solar module.” This module will often have a production tolerance of +/-5% of the rating, which means that the module can produce 95 Watts and still be called a “100-watt module.” To be conservative, it is best to use the low end of the power output spectrum as a starting point (95 Watts for a 100-watt module).
Temperature Module output power reduces as module temperature increases. When operating on a roof, a solar module will heat up substantially, reaching inner temperatures of 50-75 oC. For crystalline modules, a typical temperature reduction factor recommended by the CEC is 89% or 0.89. So the “100-watt” module will typically operate at about 85 Watts (95 Watts x 0.89 = 85 Watts) in the middle of a spring or fall day, under full sunlight conditions.
Dirt and dust Dirt and dust can accumulate on the solar module surface, blocking some of the sunlight and reducing output. Much of California has a rainy season and a dry season. Although typical dirt and dust is cleaned off during every rainy season, it is more realistic to estimate system output taking into account the reduction due to dust buildup in the dry season. A typical annual dust reduction factor to use is 93% or 0.93. So the “100watt module,” operating with some accumulated dust may operate on average at about 79 Watts (85 Watts x
0.93 = 79 Watts).
Mismatch and wiring losses The maximum power output of the total PV array is always less than the sum of the maximum output of the individual modules. This difference is a result of slight inconsistencies in performance from one module to the next and is called module mismatch and amounts to at least a 2% loss in system power. Power is also lost to resistance in the system wiring. These losses should be kept to a minimum but it is difficult to keep these losses below 3% for the system. A reasonable reduction factor for these losses is 95% or 0.95.
Dc to ac conversion losses The dc power generated by the solar module must be converted into common household ac power using an inverter. Some power is lost in the conversion process, and there are additional losses in the wires from the rooftop array down to the inverter and out to the house panel. Modern inverters commonly used in residential PV power systems have peak efficiencies of 92-94% indicated by their manufacturers, but these again are measured under well-controlled factory conditions. Actual field conditions usually result in overall dc-to-ac conversion efficiencies of about 88-92%, with 90% or 0.90 a reasonable compromise.
So the “100-watt module” output, reduced by production tolerance, heat, dust, wiring, ac conversion, and other losses will translate into about 68 Watts of AC power delivered to the house panel during the middle of
a clear day (100 Watts x 0.95 x 0.89 x 0.93 x 0.95 x 0.90 = 67 Watts).
South Sun angle and house orientation SSE,SSW During the course of a day, the angle of sunlight SE, SW striking the solar module will change, which will affect ESE,WSW the power output. The output from the “100-watt E, Wmodule” will rise from zero gradually during dawn
Flat 4:12 7:12 12:12 21:12 Vertical
0.89 0.97 1.00 0.97 0.89 0.58
0.89 0.97 0.99 0.96 0.88 0.59
0.89 0.95 0.96 0.93 0.85 0.60
0.89 0.92 0.91 0.87 0.79 0.57
0.89 0.88 0.84 0.78 0.70 0.52
hours, and increase with the sun angle to its peak Table 1: Orientation Factors for Various output at midday, and then gradually decrease into Roof Pitches and Directions the afternoon and back down to zero at night. While this variation is due in part to the changing intensity of the sun, the changing sun angle (relative to the modules) also has an effect
The pitch of the roof will affect the sun angle on the module surface, as will the East-West orientation of the roof. These effects are summarized in Table 1, which shows that an array on a 7:12-pitch roof facing due South in Southern California gives, for example, the greatest output (correction factor of 1.00), while an East facing roof at that same pitch would yield about 84% of the annual energy of the South facing roof (a correction factor of 0.84 from Table 1).
Table 2 is intended to give a conservative estimate of the annual energy expected from a typical PV system, taking into account the various factors discussed above.
These values are for annual kWh produced from a 1-kilowatt (1kW) STC DC array, as a simple and easy guide. If the system includes battery backup the output may be reduced further by 6-10% due to battery effects.
Example: A 4 kWSTC solar array (as specified under STC conditions) located in the Los Angeles area at a 4:12 pitch and facing southeast should produce at least 5343 kWh of electric energy annually (1406 kWh/kW x 0.95 x 4 kW = Table 2: Annual Energy Production 5343 kWh). The typical residential customer in that area uses about 7300 kWh annually1, meaning such a PV system by City per kWSTC array rating could produce at least 75% of the total energy needed by such a typical home. And if energy efficiency measures were taken by the owner to reduce the overall electrical consumption of the home, the percentage could approach 100%. Note that the low end of the range was used to calculate the actual savings. It is wise to be conservative when making performance claims.
| CITY | kWh/kWstc (range) |
| Arcata | 1092 - 1365 |
| Shasta | 1345 - 1681 |
| San Francisco | 1379 - 1724 |
| Sacramento | 1455 - 1819 |
| Fresno | 1505 - 1881 |
| Santa Maria | 1422 - 1778 |
| Barstow | 1646 - 2058 |
| Los Angeles | 1406 - 1758 |
| San Diego | 1406 - 1758 |
Net metering has recently been extended to time-of-use customers yielding a potential additional value of 20-30% for the PV electricity generated by the system. With this net time-of-use metering, the homeowner would cover almost their entire electric bill and only have to pay the monthly metering charge.
1 Actual residential electrical energy usage varies dramatically from one home to the next. It is best to use the previous two years of energy bills to determine actual energy consumption for a particular home. Energy consumption in California can vary from 3,000 kWh/year for a very minimal user to 25,000 kWh/year for a large home with heavy electrical usage.
2.4. Installation Labor Effort
Installation effort is very sensitive to specific house layouts and roofing type. An experienced crew can install a 2 kW non-battery PV system in two-to-four person-days. Systems with large solar arrays are relatively less effort per watt of power and kWh of energy than smaller systems because the installation of the inverter and other hardware required by all PV systems is spread over more solar modules. Systems with battery backup are more labor intensive than non-battery systems because of the additional wiring required for wiring the critical load subpanel. A battery system can add 50-100% to the time required for the installation.
2.5. Incentives to Reduce Costs
Financial incentives are available from the Energy Commission, the CPUC, and several local utilities and municipalities throughout California to reduce these system costs. The CEC buydowns are calculated by multiplying $4.50 times the adjusted peak dc power from the system in Watts (up to a maximum of 50% of the system cost). This buydown is available for all Pacific Gas & Electric (PG&E), Southern California Edison (SCE), and San Diego Gas & Electric (SDG&E) customers. Some municipal utilities in cities such as Sacramento, Los Angeles, Palo Alto, and Roseville provide the same or even higher incentives.
This level of rebate can reduce the cost of systems by 30 to 50 percent or more and result in much more favorable economics for the owner. An owner can incorporate a basic 1 kW solar power system for as little as $3,000-$5,000. If the system is included in the mortgage of the home, this small increment in house payment may be offset by an equivalent reduction in the monthly utility bill.
2.6. Estimating Electrical Energy Savings
One of the key benefits of residential solar power systems is a lower electric utility bill resulting from the energy that the solar system produces. The energy savings to a homeowner can be estimated by simply multiplying the annual energy in kWh that a PV system might produce times the utility electric energy rate. These rates vary by local utility, and are likely to increase from their current values. Estimated energy savings from small and large PV systems in Southern California are presented below to illustrate the kinds of savings that can be achieves.

2.7. Supplier and System Qualifications
When choosing a supplier and specifying a PV system, the following are a series of general guidelines to help guide the decision-making process.
2.7.1. Pre-Engineered Systems
When a owner considers an HVAC system for a home, they do not buy a compressor from one manufacturer and a cooling coil from another company, and a fan from a third company and then put these pieces together. The equipment manufacturers have engineered a packaged system that is designed to work together. Each model of a home may need a slightly different unit based on the size and layout, but those variations have been designed into the product. In the same way, the components of a PV system should be engineered to work together as a unit accounting for variations in system size for different homes.
Since the PV industry is in the early stages of development, there is a wide range of competency levels among PV system integrators. Unless the installer is familiar enough with the technology to recognize whether the system integrator is competent, it is much safer to stay with a firm that provides pre-engineered systems. Pre-engineering may not guarantee a flawless system, but the concerns over product compatibility and specification of individual components have been addressed in the system design.
2.7.2. Warranties
There are several types of warranties that come with a system or can be purchased in addition to a standard warranty. These include (1) product warranties covering defects in manufacture; (2) system warranties covering proper operation of equipment for a specific time period (5 or 10 years); and, (3) annual energy performance warranties covering the guaranteed output of the PV system. The installer, to guarantee proper system installation, often covers the system and annual energy performance warranties.
Product warranties: It is common these days to see warranties on PV modules of 20 or more years. Although this is impressive and indicates the level of confidence manufacturers place in the longevity of their products, there are many other components in these systems that may not have the same life expectancy. Inverters may have 10-year, five-year, or even one-year warranties. This must be considered when reviewing the cost of inverters and other system components.
System warranties: It is equally important to look for entire system-level warranties of five years or more. This indicates that the manufacturer has taken many other operational issues into account. Since these systems generate electrical power, it is helpful to have system performance included as part of the warranty. For instance, a typical system-level warranty might state that the system is guaranteed to produce two kilowatts (2 kW) of AC power at PVUSA Test Conditions (PTC) (PTC is 1kW/m2 irradiance, 1 m/s wind speed, 20oC ambient temperature) in the fifth year of operation. The equipment to perform this test is expensive, but the fact that a company would know enough to specify this type of warranty is an indication that they are confident in their system design. Currently, the California Energy Commission Buydown program requires installing contractor to provide these warranties. The intent of this requirement is to improve customer acceptance of PV systems.
Annual energy performance warranties: Although there are very few companies selling systems with this type of warranty, an energy performance warranty guaranties that the system will perform consistently over a period of time. This is particularly helpful in ensuring that the customer receives the bill savings that they expect. This type of warranty is more common with energy efficiency retrofit projects for commercial and industrial clients. Adequate metering to verify the system power output and energy generation is necessary to help the system owner understand whether the system is operating properly, or has warranty-related performance issues. With an adequate meter, the customer can readily identify when the system is malfunctioning.
2.7.3. Company Reputation (years in business, previous projects)
The reputation of the PV manufacturer is a critical piece of the decision-making process. The size of the company, number of years in business, number of previous projects completed, are all important issues that need to be reviewed before choosing a company’s products. Although price is often the strongest single consideration in reviewing proposals, the other less tangible considerations often add up to a similar level of importance with cost. Fortunately, there are several companies with very strong financial and historical records in this field. It is recommended that you research the background and history of the prospective vendor thoroughly.
2.8. Overall Project Coordination
Once the decision is made to install a PV system, several issues must then be addressed.
2.8.1. Utility Considerations
The electric utility company providing service to the residence plays a very important role in this process. Interconnecting a PV system to the utility grid is not a trivial undertaking. Fortunately, PV has a well-developed set of utility interconnection standards making the process fairly straightforward. However, utilities are generally cautious since most have little experience interconnecting PV systems. The key point is to involve the utility as early as possible in the installation. Most knowledgeable utilities have adopted IEEE 929-2000 Recommended Practice for Utility Interface of Photovoltaic (PV) Systems. If the utility is unfamiliar with this document, make sure that they obtain a copy and thoroughly review it.. An inverter listed to UL 1741 (with the words "Utility-Interactive" printed on the listing mark) indicates that the unit is fully compliant with IEEE 929-2000.
The other major utility-related consideration is metering requirements. In California, as in many other states, there is legislation mandating utility companies to “net-meter” a certain amount of PV systems. Net metering refers to a standard house utility meter that measures the flow of electricity in and out of the home2. California law allows customers to carry-over excess energy from month-to-month with an annual true-up and payment of the electrical bill for any net consumption over the whole year. The net metering law does not require the utility to compensate the customer for excess electricity at the end of that 12-month period. For more information about this and other consumer-related PV issues, download the document, Buying a Photovoltaic Solar Electric System: A Consumers Guide, from the California Energy Commission’s website at http://www.energy.ca.gov/reports/500-99-008.PDF or call 1-800-555-7794 (Renewable Energy Call Center) to receive a copy by mail.
2.8.2. Acceptance of Systems (performance evaluation)
Typically, the installer verifies that the system has been installed according to the manufacturer’s procedures. A checkout procedure should be developed, such as the one provided in section 4 of this guide, to ensure an efficient and complete installation. Obtaining extremely accurate performance is difficult and requires expensive test equipment. Fortunately, it is not necessary to define the performance with extreme accuracy. A system can be checked with some common test equipment to verify proper installation and performance. A key to keeping the system testing simple is to do the tests on cloudless days. Clouds can cause fluctuations that confound evaluation of the results. The PV System Installation Checklist that accompanies this guide has a detailed System Acceptance Test.
2.8.3. System Documentation
Up to this point, selection, installation, and performance of PV systems have been discussed. Of similar importance are operation and ongoing maintenance of the equipment. As with other major systems in a home, it is essential that the owner have complete documentation on the system. System documentation should include an owner’s manual and copies of relevant drawings for whatever system maintenance might be required in the future.
2.8.4. System Monitoring
The key component of the system providing feedback to the customer is the power and energy metering. Without proper metering the customer will never know whether the system is operating properly or not. A simple meter, registering the power output of the PV system and recording the energy delivered to the house, can provide the owner with the satisfaction that they can monitor the performance of the system.
Yes, out! Even a 500-Watt PV system on a sunny day may generate more electricity than the home consumes at any given time.
Maximum power output of most properly installed PV systems occurs near midday on sunny days in the spring and fall. If the owner fully understands this characteristic they will not be disappointed with unavoidable low output in the middle of the winter. The meter is also a way of proving to the owner that the equipment is properly installed. Often, the owner’s primary indication of whether they feel the system is operating properly on not is their monthly electric bill. If the owner suddenly begins using more electricity, they may not see much decrease in their bill and assume the PV system is under-performing. A meter can help avoid disputes between the installer and the owner by showing that the system performs as advertised.
One of the attractive attributes of PV system is low maintenance. However, even electrical systems need to be maintained from time to time. With proper metering, an informed owner can easily determine if their system is operating properly or not. It is important that the owner have contact information for contractors that can perform system maintenance in their area. Although many areas do not have full-time PV contractors, it is always helpful to provide a list of two or three local contractors that offer PV maintenance services. Along with the information on local contractors, the system warranty information should be provided so that the customer clearly understands what is and is not covered by their warranty.
2.9. References
1999 National Electrical Code (NEC) Article 690 and Article 702. Emerging Renewables Buy-Down Program Information: http://www.energy.ca.gov/greengrid
Buying a Photovoltaic Solar Electric System: A Consumers Guide:
http://www.energy.ca.gov/reports/500-99-008.PDF Clean Power Estimator: http://www.energy.ca.gov/cleanpower/index.html List of Certified PV Modules: http://www.energy.ca.gov/greengrid/certified_pv_modules.html List of Certified Inverters: http://www.energy.ca.gov/greengrid/certified_inverters.html California Energy Commission, 1516 9th Street, Sacramento, CA 95814-5512, 800-555-7794 (Renewable Energy Call Center)
UL Standard 1703, Standard for Flat-plate Photovoltaic Modules and Panels UL Standard 1741, Inverters, Converters, and Controllers for Independent Power Systems IEEE Standard 929-2000, Recommended Practice for Utility Interface of Photovoltaic (PV) Systems IEEE Standard 1262-1995, Recommended Practice for Qualification of Photovoltaic (PV) Modules Environmental benefits of PV systems can be found at the following USEPA website:
http://199.223.18.230/epa/rew/rew.nsf/solar/index.html
SECTION 3: SYSTEM INSTALLATION
3.1. General Recommendations
The following is a list of general recommendations to help the installer choose the right materials, equipment, and installation methods that will help ensure that the system will provide many years of reliable service. These recommendations can be used to evaluate pre-engineered system designs and compare system features from one supplier to another.
3.1.1. Materials recommendations
3.1.2. Equipment recommendations and installation methods
Main Combiner DC/AC
Service
Utility Utility Box Inverter Switch Panel
3.2. PV System Design And Installation
PV Array
3.2.1. Preparation PhaseFigure 4 Simple PV System Diagram
3.2.2. Design Phase
3.2.3. Installation Phase
Check ampacity of PV array circuits:
6. Size PV array wiring such that the maximum voltage drop at full power from the PV modules to the inverter is 3% or less (6-amps for a 100-Watt module). If array combiner box is located remote from the inverter, spread the voltage drop accordingly between the PV array-to-combiner wiring and the combiner-to-inverter wiring (example from EX-1 in the appendix: with a 100-foot wire run from PV modules to inverter (3% total) comprised of a 25-foot wire run from PV modules to combiner box and a 75-foot wire run from combiner box to inverter—use a maximum of 1% for the 25-foot run and 2% loss for the 75-foot section for a total of 3%)
7. Estimate length of wire run from inverter to main service panel (Example drawing EX-1 in the
appendix: wire run from inverter to panel is 25 feet). Example using sample drawing EX-1 in the appendix: Goal is 1% voltage drop for ac-side of system (3% absolute maximum) From 120-Volt table A-4, 1% voltage drop for 30 feet and 35 amps (to use table for 1% voltage drop, find D-Factor for 3% voltage drop for 30-amps at 30 feet (2.5), then multiply this value by 3
(7.5) to obtain proper size of wire on Table A-1), use #6 AWG wire.
3.2.4. Maintenance and Operation Phase
Following the completion of each item on the checklist below, check the box to the left of the item and insert the date and initials of the person completing the item whether that is the installing contractor or owner-installer. Remember to follow the proper safety procedures while performing the system installation. The appropriate safety equipment for each section of the checklist is listed above each section of the checklist.
Before starting any PV system testing: (hard hat and eye protection recommended)
• 1. Check that non-current carrying metal parts are grounded properly. (array frames, racks, metal boxes, etc. are connected to the grounding system)
• 2. Ensure that all labels and safety signs specified in the plans are in place.
• 3. Verify that all disconnect switches (from the main AC disconnect all the way through to the combiner fuse switches) are in the open position and tag each box with a warning sign to signify that work on the PV system is in progress.
PV ARRAY--General (hard hat, gloves, and eye protection recommended)
• 1. Verify that all combiner fuses are removed and that no voltage is present at the output of the combiner box.
• 2. Visually inspect any plug and receptacle connectors between the modules and panels to ensure they are fully engaged.
• 3. Check that strain reliefs/cable clamps are properly installed on all cables and cords by pulling on cables to verify.
• 4. Check to make sure all panels are attached properly to their mounting brackets and nothing catches the eye as being abnormal or misaligned.
• 5. Visually inspect the array for cracked modules.
• 6. Check to see that all wiring is neat and well supported.
PV ARRAY CIRCUIT WIRING (hard hat and eye protection recommended)
• 1. Check home run wires (from PV modules to combiner box) at DC string combiner box to ensure there is no voltage on them.
• 2. Recheck that fuses are removed and all switches are open.
• 3. Connect the home run wires to the DC string combiner box terminals in the proper order and make sure labeling is clearly visible.
REPETITIVE SOURCE CIRCUIT STRING WIRING (hard hat, gloves, and eye protection recommended)
The following procedure must be followed for each source circuit string in a systematic approach—i.e. east to west or north to south. Ideal testing conditions are midday on cloudless days March through October.
• 4. Check open-circuit voltage of each of the panels in the string being wired to verify that it provides the manufacturer’s specified voltage in full sun. (Panels under the same sunlight conditions should have similar voltages--beware of a 20 Volt or more shift under the same sunlight conditions.)
• 5. Verify that the both the positive and negative string connectors are identified properly with permanent wire marking.
• 6. Repeat this sequence for all source circuit strings.
CONTINUATION OF PV ARRAY CIRCUIT WIRING (hard hat, gloves, and eye protection recommended)
• 7. Recheck that DC Disconnect switch is open and tag is still intact.
• 8. VERIFY POLARITY OF EACH SOURCE CIRCUIT STRING in the DC String Combiner Box (place common lead on the negative grounding block and the positive on each string connection-pay particular attention to make sure there is NEVER a negative measurement). Verify open-circuit voltage is within proper range according to manufacturer’s installation manual and number each string and note string position on as-built drawing. (Voltages should match closely if sunlight is consistent.)
WARNING: IF POLARITY OF ONE SOURCE CIRCUIT STRING IS REVERSED, THIS CAN START A FIRE IN THE FUSE BLOCK RESULTING IN THE DESTRUCTION OF THE COMBINER BOX AND POSSIBLY ADJACENT EQUIPMENT. REVERSE POLARITY ON AN INVERTER CAN ALSO CAUSE DAMAGE THAT IS NOT COVERED UNDER THE EQUIPMENT WARRANTY.
• 9. Retighten all terminals in the DC String Combiner Box.
WIRING TESTS--Remainder of System: (hard hat, gloves, and eye protection recommended)
• 10. Verify that the only place where the AC neutral is grounded is at the main service panel.
• 11. Check the AC line voltage at main AC disconnect is within proper limits (115-125 Volts AC for 120 Volts and 230-250 for 240 Volts).
• 12. If installation contains additional AC disconnect switches repeat the step 11 voltage check on each switch working from the main service entrance to the inverter AC disconnect switch closing each switch after the test is made except for the final switch before the inverter (it is possible that the system only has a single AC switch).
INVERTER STARTUP TESTS (hard hat, gloves, and eye protection recommended)
• 1. Be sure that the inverter is off before proceeding with this section.
• 2. Test the continuity of all DC fuses to be installed in the DC string combiner box, install all string fuses, and close fused switches in combiner box.
• 3. Check open circuit voltage at DC disconnect switch to ensure it is within proper limits according to the manufacturer’s installation manual.
• 4. If installation contains additional DC disconnect switches repeat the step 4 voltage check on each switch working from the PV array to the inverter DC disconnect switch closing each switch after the test is made except for the final switch before the inverter (it is possible that the system only has a single DC switch).
• 5. At this point consult the inverter manual and follow proper startup procedure (all power to the inverter should be off at this time).
• 6. Confirm that the inverter is operating and record the DC operating voltage in the following space.________
• 7. Confirm that the operating voltage is within proper limits according to the manufacturer’s installation manual.
• 8. After recording the operating voltage at the inverter close any open boxes related to the inverter system.
• 9. Confirm that the inverter is producing the expected power output on the supplied meter.
• 10. Provide the homeowner with the initial startup test report.
SYSTEM ACCEPTANCE TEST (hard hat and eye protection recommended)
Ideal testing conditions are midday on cloudless days March through October. However, this test procedure accounts for less than ideal conditions and allows acceptance tests to be conducted on sunny winter days.
• 1. Check to make sure that the PV array is in full sun with no shading whatsoever. If it is impossible to find a time during the day when the whole array is in full sun, only that portion that is in full sun will be able to be accepted.
•
2. If the system is not operating, turn the system on and allow it to run for 15 minutesbefore taking any performance measurements.
•
3. Obtain solar irradiance measurement by one of two methods and record irradiance on this line: W/m2. To obtain percentage of peak sun, divide irradiance by 1000 W/m2 and record the value on this line . (example: 692 W/m2 ÷ 1000 W/m2 = 0.692 or 69.2%.) Method 1: Take measurement from calibrated solar meter or pyranometer. Method 2: Place a single, properly operating PV module, of the same model found in the array, in full sun in the exact same orientation as the array being tested. After 15 minutes of full exposure, test the short circuit current with a digital multimeter and place that reading on this line: Amps. Divide this number into the short circuit current (Isc) value printed on the back of the PV module and multiply this number by 1000 W/m2 and record the value on the line above. (example: Isc-measured = 3.6 Amps; Isc-printed on module = 5.2 Amps; Irradiance = 3.6 Amps/5.2 Amps * 1000 W/m2 = 692 W/m2)
• 4. Sum the total of the module ratings and place that total on this line WattsSTC. Multiply this number by 0.7 to obtain expected peak AC output and record on this line WattsAC-estimated.
• 5. Record AC Watt output from the inverter or system meter and record on this line WattsAC-measured.
• 6. Divide WattsAC-measured by percent peak irradiance and record on this line
WattsAC-corrected. This “AC-corrected” value is the rated output of PV system. This number must be within 90% or higher of WattsAC-estimated recorded in step 4. If it is less than 90%, the PV system is either shaded, dirty, miswired, fuses are blown, or the modules or inverter are not operating properly.
Example:
A PV system is made up of 20, 100 WattSTC PV modules operating at an estimated irradiance of 692 W/m2 using
method 2 shown above. The power output is measured to be 1000 WattsAC-measured at the time of the test. Is thissystem operating properly or not?
Solution:
Sum of module ratings = 100 WattsSTC per module x 20 modules = 2,000 WattsSTC. Estimated AC power output = 2,000 WattsSTC x 0.7 = 1,400 WattsAC-estimated. Measured AC output = 1,000 WattsAC-measured.
Corrected AC output = 1,020 WattsAC-corrected ÷ 0.692 = 1,474 WattsAC-corrected. Comparison of corrected and estimated outputs: 1,474 WattsAC-corrected ÷ 1,400 WattsAC-estimated = 1.05 ≥ 0.9 (acceptable performance)
APPENDIX
PV Installation Guide


+ + + + + + + + + + + + + + + +
Existing Exterior Main Breaker Box
Square-D 120 Volt QO Load Center
Minimum #6 AWG THWN Combiner Box
(2 plcs.) (Conduit size based
#10-2 conductor TC with THWN-2on wire fill)
conductors for all PV array wiring
+
POS
-
+ Photovoltaic Modules Trace Power Module
-
60 A
+
15 A, 5 plcs.
Trace C-40Continuous
Charge Controller
-
Equipment
+ Ground Surge Arrestor -
NEG
Trace No. 4/0 RHW
DC- SW4048 Inverter 250 A
AC DC+ InOut N4/0 RHW Battery Cables (Typical) No. 4/0 RHW
Exterior PG&E Disconnect Box Manual Transfer Switch in Power Module
Battery Box 1 Battery Box 2
60 A Isolated Neutral
Bonding Block
15 A 15 A20 A 20 A
N (isolated)
H
To 120 Vac House Loads
Notes:
1” EMT Conduits w/ #6 AWG THWN conductors
COMPANY NAME Title: Electrical Drawing, PV w/ Battery
| Drawn By: | Date: |
| Checked By: | Related Drawings: EX-1 |
| Scale: N/A Material: | DWG NO. EX-2 |
| TABLE A-1 | WIRE SIZING TABLE | |||||||||||||||
| FOR AMPACITY AND VOLTAGE DROP | ||||||||||||||||
| Ampacity of | Ampacity of | Ampacity of | Ampacity of | Ampacity of | Ampacity of | |||||||||||
| 90 C Wet Wire | 90 C Wet Wire | 75 C Wet Wire | 90 C Wet Wire | 75 C Wet Wire | 60 C Wet Wire | |||||||||||
| Wire Size | D Factor | Roof Mounted | Rack Mounted | Rack Mounted | BOS Wiring (45 C) | BOS Wiring (45 C) | BOS Wiring (45 C) | |||||||||
| (AWG) | Modules (80 C) | Modules (70 C) | Modules (70 C) | |||||||||||||
| 14 | 1.5 | 10 | 15 | 7 | 22 | 16 | 14 | |||||||||
| 12 | 2.5 | 12 | 17 | 8 | 26 | 21 | 18 | |||||||||
| 10 | 3.9 | 16 | 23 | 12 | 35 | 29 | 21 | |||||||||
| 8 | 6.0 | 23 | 32 | 17 | 48 | 41 | 28 | |||||||||
| 6 | 9.7 | 31 | 44 | 21 | 65 | 53 | 39 | |||||||||
| 4 | 15.6 | 39 | 55 | 28 | 83 | 70 | 50 | |||||||||
| 3 | 19 | N/A | N/A | N/A | 96 | 82 | 60 | |||||||||
| 2 | 25 | N/A | N/A | N/A | 113 | 94 | 67 | |||||||||
| 1 | 31 | N/A | N/A | N/A | 131 | 107 | 78 | |||||||||
| 1/0 | 39 | N/A | N/A | N/A | 148 | 123 | 89 | |||||||||
| 2/0 | 50 | N/A | N/A | N/A | 170 | 144 | 103 | |||||||||
| 3/0 | 62 | N/A | N/A | N/A | 196 | 164 | 117 | |||||||||
| 4/0 | 80 | N/A | N/A | N/A | 226 | 189 | 138 | |||||||||
| 300MCM | 112 | N/A | N/A | N/A | 278 | 234 | 170 | |||||||||
| 500MCM | 189 | N/A | N/A | N/A | 374 | 312 | 227 | |||||||||
| To determine D-Factor for 1% voltage drop simply multiply D-Factor from 3% tables by 3. | ||||||||||||||||
| Example: 48V, 6Amps, 70ft--D Factor = 2.9 for 3%. Multiplying by 3 yields D Factor = 8.7 | ||||||||||||||||
| Solution: Need #10 AWG to stay under 3% voltage drop and #6 to stay under 1% voltage drop | ||||||||||||||||
| To determine D-Factor for 2% voltage drop simply multiply D-Factor from 3% tables by 1.5. | ||||||||||||||||
| Example: 48V, 6Amps, 70ft--D Factor = 2.9 for 3%. Multiplying by 1.5 yields D Factor = 4.4 | ||||||||||||||||
| Solution: Need #10 AWG to stay under 3% voltage drop and #8 to stay under 2% voltage drop | ||||||||||||||||
| TABLE A-2 | D FACTOR | |||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--24-VOLT CIRCUITS-COPPER | ||||||||||||||||||||||||||
| ONE-WAY WIRE DISTANCE (FT) | ||||||||||||||||||||||||||
| AMPS | ||||||||||||||||||||||||||
| 10.0 | 20.0 | 30.0 | 40.0 | 50.0 | 60.0 | 70.0 | 80.0 | 90.0 | 100.0 | 120.0 | 140.0 | 160.0 | 180.0 | 200.0 | 220.0 | 240.0 | 260.0 | 280.0 | 300.0 | 320.0 | 340.0 | 360.0 | 380.0 | 400.0 | ||
| 2 | 0.3 | 0.6 | 0.8 | 1.1 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.1 | 6.7 | 7.2 | 7.8 | 8.3 | 8.9 | 9.4 | 10.0 | 10.6 | 11.1 | |
| 4 | 0.6 | 1.1 | 1.7 | 2.2 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 12.2 | 13.3 | 14.4 | 15.6 | 16.7 | 17.8 | 18.9 | 20.0 | 21.1 | 22.2 | |
| 6 | 0.8 | 1.7 | 2.5 | 3.3 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 16.7 | 18.3 | 20.0 | 21.7 | 23.3 | 25.0 | 26.7 | 28.3 | 30.0 | 31.7 | 33.3 | |
| 8 | 1.1 | 2.2 | 3.3 | 4.4 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 13.3 | 15.6 | 17.8 | 20.0 | 22.2 | 24.4 | 26.7 | 28.9 | 31.1 | 33.3 | 35.6 | 37.8 | 40.0 | 42.2 | 44.4 | |
| 10 | 1.4 | 2.8 | 4.2 | 5.6 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 16.7 | 19.4 | 22.2 | 25.0 | 27.8 | 30.6 | 33 | 36 | 39 | 42 | 44 | 47 | 50 | 53 | 56 | |
| 12 | 1.7 | 3.3 | 5.0 | 6.7 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 16.7 | 20.0 | 23.3 | 26.7 | 30.0 | 33.3 | 36.7 | 40 | 43 | 47 | 50 | 53 | 57 | 60 | 63 | 67 | |
| 14 | 1.9 | 3.9 | 5.8 | 7.8 | 9.7 | 11.7 | 13.6 | 15.6 | 17.5 | 19.4 | 23.3 | 27.2 | 31.1 | 35.0 | 38.9 | 42.8 | 47 | 51 | 54 | 58 | 62 | 66 | 70 | 74 | 78 | |
| 16 | 2.2 | 4.4 | 6.7 | 8.9 | 11.1 | 13.3 | 15.6 | 17.8 | 20.0 | 22.2 | 26.7 | 31.1 | 35.6 | 40.0 | 44.4 | 48.9 | 53 | 58 | 62 | 67 | 71 | 76 | 80 | 84 | 89 | |
| 18 | 2.5 | 5.0 | 7.5 | 10.0 | 12.5 | 15.0 | 17.5 | 20.0 | 22.5 | 25.0 | 30.0 | 35.0 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | |
| 20 | 2.8 | 5.6 | 8.3 | 11.1 | 13.9 | 16.7 | 19.4 | 22.2 | 25.0 | 27.8 | 33.3 | 38.9 | 44 | 50 | 56 | 61 | 67 | 72 | 78 | 83 | 89 | 94 | 100 | 106 | 111 | |
| 25 | 3.5 | 6.9 | 10.4 | 13.9 | 17.4 | 20.8 | 24.3 | 27.8 | 31.3 | 34.7 | 41.7 | 48.6 | 56 | 63 | 69 | 76 | 83 | 90 | 97 | 104 | 111 | 118 | 125 | 132 | 139 | |
| 30 | 4.2 | 8.3 | 12.5 | 16.7 | 20.8 | 25.0 | 29.2 | 33 | 38 | 42 | 50 | 58 | 67 | 75 | 83 | 92 | 100 | 108 | 117 | 125 | 133 | 142 | 150 | 158 | 167 | |
| 35 | 4.9 | 9.7 | 14.6 | 19.4 | 24.3 | 29.2 | 34.0 | 39 | 44 | 49 | 58 | 68 | 78 | 88 | 97 | 107 | 117 | 126 | 136 | 146 | 156 | 165 | 175 | 185 | 194 | |
| 40 | 5.6 | 11.1 | 16.7 | 22.2 | 27.8 | 33.3 | 38.9 | 44 | 50 | 56 | 67 | 78 | 89 | 100 | 111 | 122 | 133 | 144 | 156 | 167 | 178 | 189 | 200 | 211 | 222 | |
| 45 | 6.3 | 12.5 | 18.8 | 25.0 | 31.3 | 38 | 44 | 50 | 56 | 63 | 75 | 88 | 100 | 113 | 125 | 138 | 150 | 163 | 175 | 188 | 200 | 213 | 225 | 238 | 250 | |
| 50 | 6.9 | 13.9 | 20.8 | 27.8 | 34.7 | 42 | 49 | 56 | 63 | 69 | 83 | 97 | 111 | 125 | 139 | 153 | 167 | 181 | 194 | 208 | 222 | 236 | 250 | 264 | 278 | |
| 60 | 8.3 | 16.7 | 25.0 | 33 | 42 | 50 | 58 | 67 | 75 | 83 | 100 | 117 | 133 | 150 | 167 | 183 | 200 | 217 | 233 | 250 | 267 | 283 | 300 | 317 | 333 | |
| 70 | 9.7 | 19.4 | 29.2 | 39 | 49 | 58 | 68 | 78 | 88 | 97 | 117 | 136 | 156 | 175 | 194 | 214 | 233 | 253 | 272 | 292 | 311 | 331 | 350 | 369 | 389 | |
| 80 | 11.1 | 22.2 | 33.3 | 44 | 56 | 67 | 78 | 89 | 100 | 111 | 133 | 156 | 178 | 200 | 222 | 244 | 267 | 289 | 311 | 333 | 356 | 378 | 400 | 422 | 444 | |
| 90 | 12.5 | 25.0 | 37.5 | 50 | 63 | 75 | 88 | 100 | 113 | 125 | 150 | 175 | 200 | 225 | 250 | 275 | 300 | 325 | 350 | 375 | 400 | 425 | 450 | 475 | 500 | |
| 100 | 13.9 | 27.8 | 41.7 | 56 | 69 | 83 | 97 | 111 | 125 | 139 | 167 | 194 | 222 | 250 | 278 | 306 | 333 | 361 | 389 | 417 | 444 | 472 | 500 | 528 | 556 | |
| 110 | 15.3 | 30.6 | 45.8 | 61 | 76 | 92 | 107 | 122 | 138 | 153 | 183 | 214 | 244 | 275 | 306 | 336 | 367 | 397 | 428 | 458 | 489 | 519 | 550 | 581 | 611 | |
| 120 | 16.7 | 33 | 50 | 67 | 83 | 100 | 117 | 133 | 150 | 167 | 200 | 233 | 267 | 300 | 333 | 367 | 400 | 433 | 467 | 500 | 533 | 567 | 600 | 633 | 667 | |
| 130 | 18.1 | 36 | 54 | 72 | 90 | 108 | 126 | 144 | 163 | 181 | 217 | 253 | 289 | 325 | 361 | 397 | 433 | 469 | 506 | 542 | 578 | 614 | 650 | 686 | 722 | |
| 140 | 19.4 | 39 | 58 | 78 | 97 | 117 | 136 | 156 | 175 | 194 | 233 | 272 | 311 | 350 | 389 | 428 | 467 | 506 | 544 | 583 | 622 | 661 | 700 | 739 | 778 | |
| 150 | 20.8 | 42 | 63 | 83 | 104 | 125 | 146 | 167 | 188 | 208 | 250 | 292 | 333 | 375 | 417 | 458 | 500 | 542 | 583 | 625 | 667 | 708 | 750 | 792 | 833 | |
| 160 | 22.2 | 44 | 67 | 89 | 111 | 133 | 156 | 178 | 200 | 222 | 267 | 311 | 356 | 400 | 444 | 489 | 533 | 578 | 622 | 667 | 711 | 756 | 800 | 844 | 889 | |
| 170 | 23.6 | 47 | 71 | 94 | 118 | 142 | 165 | 189 | 213 | 236 | 283 | 331 | 378 | 425 | 472 | 519 | 567 | 614 | 661 | 708 | 756 | 803 | 850 | 897 | 944 | |
| 180 | 25.0 | 50 | 75 | 100 | 125 | 150 | 175 | 200 | 225 | 250 | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 650 | 700 | 750 | 800 | 850 | 900 | 950 | 1000 | |
| 190 | 26.4 | 53 | 79 | 106 | 132 | 158 | 185 | 211 | 238 | 264 | 317 | 369 | 422 | 475 | 528 | 581 | 633 | 686 | 739 | 792 | 844 | 897 | 950 | 1003 | 1056 | |
| 200 | 27.8 | 56 | 83 | 111 | 139 | 167 | 194 | 222 | 250 | 278 | 333 | 389 | 444 | 500 | 556 | 611 | 667 | 722 | 778 | 833 | 889 | 944 | 1000 | 1056 | 1111 | |
| TABLE A-3 | D FACTOR | |||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--48-VOLT CIRCUITS-COPPER | ||||||||||||||||||||||||||
| ONE-WAY WIRE DISTANCE (FT) | ||||||||||||||||||||||||||
| AMPS | ||||||||||||||||||||||||||
| 10.0 | 20.0 | 30.0 | 40.0 | 50.0 | 60.0 | 70.0 | 80.0 | 90.0 | 100.0 | 120.0 | 140.0 | 160.0 | 180.0 | 200.0 | 220.0 | 240.0 | 260.0 | 280.0 | 300.0 | 320.0 | 340.0 | 360.0 | 380.0 | 400.0 | ||
| 2 | 0.1 | 0.3 | 0.4 | 0.6 | 0.7 | 0.8 | 1.0 | 1.1 | 1.3 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.1 | 3.3 | 3.6 | 3.9 | 4.2 | 4.4 | 4.7 | 5.0 | 5.3 | 5.6 | |
| 4 | 0.3 | 0.6 | 0.8 | 1.1 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.1 | 6.7 | 7.2 | 7.8 | 8.3 | 8.9 | 9.4 | 10.0 | 10.6 | 11.1 | |
| 6 | 0.4 | 0.8 | 1.3 | 1.7 | 2.1 | 2.5 | 2.9 | 3.3 | 3.8 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 9.2 | 10.0 | 10.8 | 11.7 | 12.5 | 13.3 | 14.2 | 15.0 | 15.8 | 16.7 | |
| 8 | 0.6 | 1.1 | 1.7 | 2.2 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 12.2 | 13.3 | 14.4 | 15.6 | 16.7 | 17.8 | 18.9 | 20.0 | 21.1 | 22.2 | |
| 10 | 0.7 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 4.9 | 5.6 | 6.3 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 15.3 | 17 | 18 | 19 | 21 | 22 | 24 | 25 | 26 | 28 | |
| 12 | 0.8 | 1.7 | 2.5 | 3.3 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 16.7 | 18.3 | 20 | 22 | 23 | 25 | 27 | 28 | 30 | 32 | 33 | |
| 14 | 1.0 | 1.9 | 2.9 | 3.9 | 4.9 | 5.8 | 6.8 | 7.8 | 8.8 | 9.7 | 11.7 | 13.6 | 15.6 | 17.5 | 19.4 | 21.4 | 23 | 25 | 27 | 29 | 31 | 33 | 35 | 37 | 39 | |
| 16 | 1.1 | 2.2 | 3.3 | 4.4 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 13.3 | 15.6 | 17.8 | 20.0 | 22.2 | 24.4 | 27 | 29 | 31 | 33 | 36 | 38 | 40 | 42 | 44 | |
| 18 | 1.3 | 2.5 | 3.8 | 5.0 | 6.3 | 7.5 | 8.8 | 10.0 | 11.3 | 12.5 | 15.0 | 17.5 | 20 | 23 | 25 | 28 | 30 | 33 | 35 | 38 | 40 | 43 | 45 | 48 | 50 | |
| 20 | 1.4 | 2.8 | 4.2 | 5.6 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 16.7 | 19.4 | 22 | 25 | 28 | 31 | 33 | 36 | 39 | 42 | 44 | 47 | 50 | 53 | 56 | |
| 25 | 1.7 | 3.5 | 5.2 | 6.9 | 8.7 | 10.4 | 12.2 | 13.9 | 15.6 | 17.4 | 20.8 | 24.3 | 28 | 31 | 35 | 38 | 42 | 45 | 49 | 52 | 56 | 59 | 63 | 66 | 69 | |
| 30 | 2.1 | 4.2 | 6.3 | 8.3 | 10.4 | 12.5 | 14.6 | 17 | 19 | 21 | 25 | 29 | 33 | 38 | 42 | 46 | 50 | 54 | 58 | 63 | 67 | 71 | 75 | 79 | 83 | |
| 35 | 2.4 | 4.9 | 7.3 | 9.7 | 12.2 | 14.6 | 17.0 | 19 | 22 | 24 | 29 | 34 | 39 | 44 | 49 | 53 | 58 | 63 | 68 | 73 | 78 | 83 | 88 | 92 | 97 | |
| 40 | 2.8 | 5.6 | 8.3 | 11.1 | 13.9 | 16.7 | 19.4 | 22 | 25 | 28 | 33 | 39 | 44 | 50 | 56 | 61 | 67 | 72 | 78 | 83 | 89 | 94 | 100 | 106 | 111 | |
| 45 | 3.1 | 6.3 | 9.4 | 12.5 | 15.6 | 19 | 22 | 25 | 28 | 31 | 38 | 44 | 50 | 56 | 63 | 69 | 75 | 81 | 88 | 94 | 100 | 106 | 113 | 119 | 125 | |
| 50 | 3.5 | 6.9 | 10.4 | 13.9 | 17.4 | 21 | 24 | 28 | 31 | 35 | 42 | 49 | 56 | 63 | 69 | 76 | 83 | 90 | 97 | 104 | 111 | 118 | 125 | 132 | 139 | |
| 60 | 4.2 | 8.3 | 12.5 | 17 | 21 | 25 | 29 | 33 | 38 | 42 | 50 | 58 | 67 | 75 | 83 | 92 | 100 | 108 | 117 | 125 | 133 | 142 | 150 | 158 | 167 | |
| 70 | 4.9 | 9.7 | 14.6 | 19 | 24 | 29 | 34 | 39 | 44 | 49 | 58 | 68 | 78 | 88 | 97 | 107 | 117 | 126 | 136 | 146 | 156 | 165 | 175 | 185 | 194 | |
| 80 | 5.6 | 11.1 | 16.7 | 22 | 28 | 33 | 39 | 44 | 50 | 56 | 67 | 78 | 89 | 100 | 111 | 122 | 133 | 144 | 156 | 167 | 178 | 189 | 200 | 211 | 222 | |
| 90 | 6.3 | 12.5 | 18.8 | 25 | 31 | 38 | 44 | 50 | 56 | 63 | 75 | 88 | 100 | 113 | 125 | 138 | 150 | 163 | 175 | 188 | 200 | 213 | 225 | 238 | 250 | |
| 100 | 6.9 | 13.9 | 20.8 | 28 | 35 | 42 | 49 | 56 | 63 | 69 | 83 | 97 | 111 | 125 | 139 | 153 | 167 | 181 | 194 | 208 | 222 | 236 | 250 | 264 | 278 | |
| 110 | 7.6 | 15.3 | 22.9 | 31 | 38 | 46 | 53 | 61 | 69 | 76 | 92 | 107 | 122 | 138 | 153 | 168 | 183 | 199 | 214 | 229 | 244 | 260 | 275 | 290 | 306 | |
| 120 | 8.3 | 17 | 25 | 33 | 42 | 50 | 58 | 67 | 75 | 83 | 100 | 117 | 133 | 150 | 167 | 183 | 200 | 217 | 233 | 250 | 267 | 283 | 300 | 317 | 333 | |
| 130 | 9.0 | 18 | 27 | 36 | 45 | 54 | 63 | 72 | 81 | 90 | 108 | 126 | 144 | 163 | 181 | 199 | 217 | 235 | 253 | 271 | 289 | 307 | 325 | 343 | 361 | |
| 140 | 9.7 | 19 | 29 | 39 | 49 | 58 | 68 | 78 | 88 | 97 | 117 | 136 | 156 | 175 | 194 | 214 | 233 | 253 | 272 | 292 | 311 | 331 | 350 | 369 | 389 | |
| 150 | 10.4 | 21 | 31 | 42 | 52 | 63 | 73 | 83 | 94 | 104 | 125 | 146 | 167 | 188 | 208 | 229 | 250 | 271 | 292 | 313 | 333 | 354 | 375 | 396 | 417 | |
| 160 | 11.1 | 22 | 33 | 44 | 56 | 67 | 78 | 89 | 100 | 111 | 133 | 156 | 178 | 200 | 222 | 244 | 267 | 289 | 311 | 333 | 356 | 378 | 400 | 422 | 444 | |
| 170 | 11.8 | 24 | 35 | 47 | 59 | 71 | 83 | 94 | 106 | 118 | 142 | 165 | 189 | 213 | 236 | 260 | 283 | 307 | 331 | 354 | 378 | 401 | 425 | 449 | 472 | |
| 180 | 12.5 | 25 | 38 | 50 | 63 | 75 | 88 | 100 | 113 | 125 | 150 | 175 | 200 | 225 | 250 | 275 | 300 | 325 | 350 | 375 | 400 | 425 | 450 | 475 | 500 | |
| 190 | 13.2 | 26 | 40 | 53 | 66 | 79 | 92 | 106 | 119 | 132 | 158 | 185 | 211 | 238 | 264 | 290 | 317 | 343 | 369 | 396 | 422 | 449 | 475 | 501 | 528 | |
| 200 | 13.9 | 28 | 42 | 56 | 69 | 83 | 97 | 111 | 125 | 139 | 167 | 194 | 222 | 250 | 278 | 306 | 333 | 361 | 389 | 417 | 444 | 472 | 500 | 528 | 556 | |
| TABLE A-4 | D FACTOR | |||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--120-VOLT CIRCUITS-COPPER | ||||||||||||||||||||||||||
| ONE-WAY WIRE DISTANCE (FT) | ||||||||||||||||||||||||||
| AMPS | ||||||||||||||||||||||||||
| 10.0 | 20.0 | 30.0 | 40.0 | 50.0 | 60.0 | 70.0 | 80.0 | 90.0 | 100.0 | 120.0 | 140.0 | 160.0 | 180.0 | 200.0 | 220.0 | 240.0 | 260.0 | 280.0 | 300.0 | 320.0 | 340.0 | 360.0 | 380.0 | 400.0 | ||
| 2 | 0.1 | 0.1 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | 1.1 | 1.2 | 1.3 | 1.4 | 1.6 | 1.7 | 1.8 | 1.9 | 2.0 | 2.1 | 2.2 | |
| 4 | 0.1 | 0.2 | 0.3 | 0.4 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | 1.1 | 1.3 | 1.6 | 1.8 | 2.0 | 2.2 | 2.4 | 2.7 | 2.9 | 3.1 | 3.3 | 3.6 | 3.8 | 4.0 | 4.2 | 4.4 | |
| 6 | 0.2 | 0.3 | 0.5 | 0.7 | 0.8 | 1.0 | 1.2 | 1.3 | 1.5 | 1.7 | 2.0 | 2.3 | 2.7 | 3.0 | 3.3 | 3.7 | 4.0 | 4.3 | 4.7 | 5.0 | 5.3 | 5.7 | 6.0 | 6.3 | 6.7 | |
| 8 | 0.2 | 0.4 | 0.7 | 0.9 | 1.1 | 1.3 | 1.6 | 1.8 | 2.0 | 2.2 | 2.7 | 3.1 | 3.6 | 4.0 | 4.4 | 4.9 | 5.3 | 5.8 | 6.2 | 6.7 | 7.1 | 7.6 | 8.0 | 8.4 | 8.9 | |
| 10 | 0.3 | 0.6 | 0.8 | 1.1 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.1 | 6.7 | 7.2 | 7.8 | 8.3 | 8.9 | 9.4 | 10.0 | 10.6 | 11.1 | |
| 12 | 0.3 | 0.7 | 1.0 | 1.3 | 1.7 | 2.0 | 2.3 | 2.7 | 3.0 | 3.3 | 4.0 | 4.7 | 5.3 | 6.0 | 6.7 | 7.3 | 8.0 | 8.7 | 9.3 | 10.0 | 10.7 | 11.3 | 12.0 | 12.7 | 13.3 | |
| 14 | 0.4 | 0.8 | 1.2 | 1.6 | 1.9 | 2.3 | 2.7 | 3.1 | 3.5 | 3.9 | 4.7 | 5.4 | 6.2 | 7.0 | 7.8 | 8.6 | 9.3 | 10.1 | 10.9 | 11.7 | 12.4 | 13.2 | 14.0 | 14.8 | 15.6 | |
| 16 | 0.4 | 0.9 | 1.3 | 1.8 | 2.2 | 2.7 | 3.1 | 3.6 | 4.0 | 4.4 | 5.3 | 6.2 | 7.1 | 8.0 | 8.9 | 9.8 | 10.7 | 11.6 | 12.4 | 13.3 | 14.2 | 15.1 | 16.0 | 16.9 | 17.8 | |
| 18 | 0.5 | 1.0 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 | 4.0 | 4.5 | 5.0 | 6.0 | 7.0 | 8.0 | 9.0 | 10.0 | 11.0 | 12.0 | 13.0 | 14.0 | 15.0 | 16.0 | 17.0 | 18.0 | 19.0 | 20.0 | |
| 20 | 0.6 | 1.1 | 1.7 | 2.2 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 12.2 | 13.3 | 14.4 | 15.6 | 16.7 | 17.8 | 18.9 | 20.0 | 21.1 | 22.2 | |
| 25 | 0.7 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 4.9 | 5.6 | 6.3 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 14 | 15 | 17 | 18 | 19 | 21 | 22 | 24 | 25 | 26 | 28 | |
| 30 | 0.8 | 1.7 | 2.5 | 3.3 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 17 | 18 | 20 | 22 | 23 | 25 | 27 | 28 | 30 | 32 | 33 | |
| 35 | 1.0 | 1.9 | 2.9 | 3.9 | 4.9 | 5.8 | 6.8 | 7.8 | 8.8 | 9.7 | 11.7 | 13.6 | 15.6 | 17.5 | 19 | 21 | 23 | 25 | 27 | 29 | 31 | 33 | 35 | 37 | 39 | |
| 40 | 1.1 | 2.2 | 3.3 | 4.4 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 13.3 | 15.6 | 17.8 | 20.0 | 22 | 24 | 27 | 29 | 31 | 33 | 36 | 38 | 40 | 42 | 44 | |
| 45 | 1.3 | 2.5 | 3.8 | 5.0 | 6.3 | 7.5 | 8.8 | 10.0 | 11.3 | 12.5 | 15.0 | 17.5 | 20.0 | 22.5 | 25 | 28 | 30 | 33 | 35 | 38 | 40 | 43 | 45 | 48 | 50 | |
| 50 | 1.4 | 2.8 | 4.2 | 5.6 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 16.7 | 19.4 | 22.2 | 25.0 | 28 | 31 | 33 | 36 | 39 | 42 | 44 | 47 | 50 | 53 | 56 | |
| 60 | 1.7 | 3.3 | 5.0 | 6.7 | 8.3 | 10.0 | 11.7 | 13 | 15 | 17 | 20 | 23 | 27 | 30 | 33 | 37 | 40 | 43 | 47 | 50 | 53 | 57 | 60 | 63 | 67 | |
| 70 | 1.9 | 3.9 | 5.8 | 7.8 | 9.7 | 11.7 | 13.6 | 16 | 18 | 19 | 23 | 27 | 31 | 35 | 39 | 43 | 47 | 51 | 54 | 58 | 62 | 66 | 70 | 74 | 78 | |
| 80 | 2.2 | 4.4 | 6.7 | 8.9 | 11.1 | 13.3 | 15.6 | 18 | 20 | 22 | 27 | 31 | 36 | 40 | 44 | 49 | 53 | 58 | 62 | 67 | 71 | 76 | 80 | 84 | 89 | |
| 90 | 2.5 | 5.0 | 7.5 | 10.0 | 12.5 | 15.0 | 17.5 | 20 | 23 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | |
| 100 | 2.8 | 5.6 | 8.3 | 11.1 | 13.9 | 16.7 | 19.4 | 22 | 25 | 28 | 33 | 39 | 44 | 50 | 56 | 61 | 67 | 72 | 78 | 83 | 89 | 94 | 100 | 106 | 111 | |
| 110 | 3.1 | 6.1 | 9.2 | 12.2 | 15.3 | 18.3 | 21.4 | 24 | 28 | 31 | 37 | 43 | 49 | 55 | 61 | 67 | 73 | 79 | 86 | 92 | 98 | 104 | 110 | 116 | 122 | |
| 120 | 3.3 | 6.7 | 10.0 | 13.3 | 16.7 | 20.0 | 23.3 | 27 | 30 | 33 | 40 | 47 | 53 | 60 | 67 | 73 | 80 | 87 | 93 | 100 | 107 | 113 | 120 | 127 | 133 | |
| 130 | 3.6 | 7.2 | 10.8 | 14.4 | 18.1 | 21.7 | 25.3 | 29 | 33 | 36 | 43 | 51 | 58 | 65 | 72 | 79 | 87 | 94 | 101 | 108 | 116 | 123 | 130 | 137 | 144 | |
| 140 | 3.9 | 7.8 | 11.7 | 16 | 19 | 23 | 27 | 31 | 35 | 39 | 47 | 54 | 62 | 70 | 78 | 86 | 93 | 101 | 109 | 117 | 124 | 132 | 140 | 148 | 156 | |
| 150 | 4.2 | 8.3 | 12.5 | 17 | 21 | 25 | 29 | 33 | 38 | 42 | 50 | 58 | 67 | 75 | 83 | 92 | 100 | 108 | 117 | 125 | 133 | 142 | 150 | 158 | 167 | |
| 160 | 4.4 | 8.9 | 13.3 | 18 | 22 | 27 | 31 | 36 | 40 | 44 | 53 | 62 | 71 | 80 | 89 | 98 | 107 | 116 | 124 | 133 | 142 | 151 | 160 | 169 | 178 | |
| 170 | 4.7 | 9.4 | 14.2 | 19 | 24 | 28 | 33 | 38 | 43 | 47 | 57 | 66 | 76 | 85 | 94 | 104 | 113 | 123 | 132 | 142 | 151 | 161 | 170 | 179 | 189 | |
| 180 | 5.0 | 10.0 | 15.0 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 60 | 70 | 80 | 90 | 100 | 110 | 120 | 130 | 140 | 150 | 160 | 170 | 180 | 190 | 200 | |
| 190 | 5.3 | 10.6 | 15.8 | 21 | 26 | 32 | 37 | 42 | 48 | 53 | 63 | 74 | 84 | 95 | 106 | 116 | 127 | 137 | 148 | 158 | 169 | 179 | 190 | 201 | 211 | |
| 200 | 5.6 | 11.1 | 16.7 | 22 | 28 | 33 | 39 | 44 | 50 | 56 | 67 | 78 | 89 | 100 | 111 | 122 | 133 | 144 | 156 | 167 | 178 | 189 | 200 | 211 | 222 | |
| TABLE A-5 | D FACTOR | |||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--240-VOLT CIRCUITS-COPPER | ||||||||||||||||||||||||||
| ONE-WAY WIRE DISTANCE (FT) | ||||||||||||||||||||||||||
| 10 | 20 | 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 120 | 140 | 160 | 180 | 200 | 220 | 240 | 260 | 280 | 300 | 320 | 340 | 360 | 380 | 400 | ||
| AMPS | ||||||||||||||||||||||||||
| 2 | 0.0 | 0.1 | 0.1 | 0.1 | 0.1 | 0.2 | 0.2 | 0.2 | 0.3 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 | 0.6 | 0.6 | 0.7 | 0.7 | 0.8 | 0.8 | 0.9 | 0.9 | 1.0 | 1.1 | 1.1 | |
| 4 | 0.1 | 0.1 | 0.2 | 0.2 | 0.3 | 0.3 | 0.4 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | 1.1 | 1.2 | 1.3 | 1.4 | 1.6 | 1.7 | 1.8 | 1.9 | 2.0 | 2.1 | 2.2 | |
| 6 | 0.1 | 0.2 | 0.3 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.8 | 1.0 | 1.2 | 1.3 | 1.5 | 1.7 | 1.8 | 2.0 | 2.2 | 2.3 | 2.5 | 2.7 | 2.8 | 3.0 | 3.2 | 3.3 | |
| 8 | 0.1 | 0.2 | 0.3 | 0.4 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | 1.1 | 1.3 | 1.6 | 1.8 | 2.0 | 2.2 | 2.4 | 2.7 | 2.9 | 3.1 | 3.3 | 3.6 | 3.8 | 4.0 | 4.2 | 4.4 | |
| 10 | 0.1 | 0.3 | 0.4 | 0.6 | 0.7 | 0.8 | 1.0 | 1.1 | 1.3 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.1 | 3.3 | 3.6 | 3.9 | 4.2 | 4.4 | 4.7 | 5.0 | 5.3 | 5.6 | |
| 12 | 0.2 | 0.3 | 0.5 | 0.7 | 0.8 | 1.0 | 1.2 | 1.3 | 1.5 | 1.7 | 2.0 | 2.3 | 2.7 | 3.0 | 3.3 | 3.7 | 4.0 | 4.3 | 4.7 | 5.0 | 5.3 | 5.7 | 6.0 | 6.3 | 6.7 | |
| 14 | 0.2 | 0.4 | 0.6 | 0.8 | 1.0 | 1.2 | 1.4 | 1.6 | 1.8 | 1.9 | 2.3 | 2.7 | 3.1 | 3.5 | 3.9 | 4.3 | 4.7 | 5.1 | 5.4 | 5.8 | 6.2 | 6.6 | 7.0 | 7.4 | 7.8 | |
| 16 | 0.2 | 0.4 | 0.7 | 0.9 | 1.1 | 1.3 | 1.6 | 1.8 | 2.0 | 2.2 | 2.7 | 3.1 | 3.6 | 4.0 | 4.4 | 4.9 | 5.3 | 5.8 | 6.2 | 6.7 | 7.1 | 7.6 | 8.0 | 8.4 | 8.9 | |
| 18 | 0.3 | 0.5 | 0.8 | 1.0 | 1.3 | 1.5 | 1.8 | 2.0 | 2.3 | 2.5 | 3.0 | 3.5 | 4.0 | 4.5 | 5.0 | 5.5 | 6.0 | 6.5 | 7.0 | 7.5 | 8.0 | 8.5 | 9.0 | 9.5 | 10.0 | |
| 20 | 0.3 | 0.6 | 0.8 | 1.1 | 1.4 | 1.7 | 1.9 | 2.2 | 2.5 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.1 | 6.7 | 7.2 | 7.8 | 8.3 | 8.9 | 9.4 | 10.0 | 10.6 | 11.1 | |
| 25 | 0.3 | 0.7 | 1.0 | 1.4 | 1.7 | 2.1 | 2.4 | 2.8 | 3.1 | 3.5 | 4.2 | 4.9 | 5.6 | 6.3 | 6.9 | 7.6 | 8.3 | 9.0 | 9.7 | 10.4 | 11.1 | 11.8 | 12.5 | 13.2 | 13.9 | |
| 30 | 0.4 | 0.8 | 1.3 | 1.7 | 2.1 | 2.5 | 2.9 | 3.3 | 3.8 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 9.2 | 10.0 | 10.8 | 11.7 | 12.5 | 13.3 | 14.2 | 15.0 | 16 | 17 | |
| 35 | 0.5 | 1.0 | 1.5 | 1.9 | 2.4 | 2.9 | 3.4 | 3.9 | 4.4 | 4.9 | 5.8 | 6.8 | 7.8 | 8.8 | 9.7 | 10.7 | 11.7 | 12.6 | 13.6 | 14.6 | 15.6 | 16.5 | 17.5 | 18 | 19 | |
| 40 | 0.6 | 1.1 | 1.7 | 2.2 | 2.8 | 3.3 | 3.9 | 4.4 | 5.0 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 12.2 | 13.3 | 14.4 | 15.6 | 16.7 | 17.8 | 18.9 | 20.0 | 21 | 22 | |
| 45 | 0.6 | 1.3 | 1.9 | 2.5 | 3.1 | 3.8 | 4.4 | 5.0 | 5.6 | 6.3 | 7.5 | 8.8 | 10.0 | 11.3 | 12.5 | 13.8 | 15.0 | 16 | 18 | 19 | 20 | 21 | 23 | 24 | 25 | |
| 50 | 0.7 | 1.4 | 2.1 | 2.8 | 3.5 | 4.2 | 4.9 | 5.6 | 6.3 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 15.3 | 16.7 | 18 | 19 | 21 | 22 | 24 | 25 | 26 | 28 | |
| 60 | 0.8 | 1.7 | 2.5 | 3.3 | 4.2 | 5.0 | 5.8 | 6.7 | 7.5 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 17 | 18 | 20 | 22 | 23 | 25 | 27 | 28 | 30 | 32 | 33 | |
| 70 | 1.0 | 1.9 | 2.9 | 3.9 | 4.9 | 5.8 | 6.8 | 7.8 | 8.8 | 9.7 | 11.7 | 13.6 | 15.6 | 17.5 | 19 | 21 | 23 | 25 | 27 | 29 | 31 | 33 | 35 | 37 | 39 | |
| 80 | 1.1 | 2.2 | 3.3 | 4.4 | 5.6 | 6.7 | 7.8 | 8.9 | 10.0 | 11.1 | 13.3 | 15.6 | 17.8 | 20.0 | 22 | 24 | 27 | 29 | 31 | 33 | 36 | 38 | 40 | 42 | 44 | |
| 90 | 1.3 | 2.5 | 3.8 | 5.0 | 6.3 | 7.5 | 8.8 | 10.0 | 11.3 | 12.5 | 15.0 | 17.5 | 20.0 | 22.5 | 25 | 28 | 30 | 33 | 35 | 38 | 40 | 43 | 45 | 48 | 50 | |
| 100 | 1.4 | 2.8 | 4.2 | 5.6 | 6.9 | 8.3 | 9.7 | 11.1 | 12.5 | 13.9 | 16.7 | 19.4 | 22.2 | 25.0 | 28 | 31 | 33 | 36 | 39 | 42 | 44 | 47 | 50 | 53 | 56 | |
| 110 | 1.5 | 3.1 | 4.6 | 6.1 | 7.6 | 9.2 | 10.7 | 12.2 | 13.8 | 15.3 | 18.3 | 21.4 | 24.4 | 27.5 | 31 | 34 | 37 | 40 | 43 | 46 | 49 | 52 | 55 | 58 | 61 | |
| 120 | 1.7 | 3.3 | 5.0 | 6.7 | 8.3 | 10.0 | 11.7 | 13.3 | 15.0 | 17 | 20 | 23 | 27 | 30 | 33 | 37 | 40 | 43 | 47 | 50 | 53 | 57 | 60 | 63 | 67 | |
| 130 | 1.8 | 3.6 | 5.4 | 7.2 | 9.0 | 10.8 | 12.6 | 14.4 | 16.3 | 18 | 22 | 25 | 29 | 33 | 36 | 40 | 43 | 47 | 51 | 54 | 58 | 61 | 65 | 69 | 72 | |
| 140 | 1.9 | 3.9 | 5.8 | 7.8 | 9.7 | 11.7 | 13.6 | 15.6 | 17.5 | 19 | 23 | 27 | 31 | 35 | 39 | 43 | 47 | 51 | 54 | 58 | 62 | 66 | 70 | 74 | 78 | |
| 150 | 2.1 | 4.2 | 6.3 | 8.3 | 10.4 | 12.5 | 14.6 | 17 | 19 | 21 | 25 | 29 | 33 | 38 | 42 | 46 | 50 | 54 | 58 | 63 | 67 | 71 | 75 | 79 | 83 | |
| 160 | 2.2 | 4.4 | 6.7 | 8.9 | 11.1 | 13.3 | 15.6 | 18 | 20 | 22 | 27 | 31 | 36 | 40 | 44 | 49 | 53 | 58 | 62 | 67 | 71 | 76 | 80 | 84 | 89 | |
| 170 | 2.4 | 4.7 | 7.1 | 9.4 | 11.8 | 14.2 | 16.5 | 19 | 21 | 24 | 28 | 33 | 38 | 43 | 47 | 52 | 57 | 61 | 66 | 71 | 76 | 80 | 85 | 90 | 94 | |
| 180 | 2.5 | 5.0 | 7.5 | 10.0 | 12.5 | 15.0 | 17.5 | 20 | 23 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 | |
| 190 | 2.6 | 5.3 | 7.9 | 10.6 | 13.2 | 16 | 18 | 21 | 24 | 26 | 32 | 37 | 42 | 48 | 53 | 58 | 63 | 69 | 74 | 79 | 84 | 90 | 95 | 100 | 106 | |
| 200 | 2.8 | 5.6 | 8.3 | 11.1 | 13.9 | 17 | 19 | 22 | 25 | 28 | 33 | 39 | 44 | 50 | 56 | 61 | 67 | 72 | 78 | 83 | 89 | 94 | 100 | 106 | 111 | |
| 210 | 2.9 | 5.8 | 8.8 | 11.7 | 14.6 | 18 | 20 | 23 | 26 | 29 | 35 | 41 | 47 | 53 | 58 | 64 | 70 | 76 | 82 | 88 | 93 | 99 | 105 | 111 | 117 | |
| 220 | 3.1 | 6.1 | 9.2 | 12.2 | 15.3 | 18 | 21 | 24 | 28 | 31 | 37 | 43 | 49 | 55 | 61 | 67 | 73 | 79 | 86 | 92 | 98 | 104 | 110 | 116 | 122 | |
| 230 | 3.2 | 6.4 | 9.6 | 12.8 | 16.0 | 19 | 22 | 26 | 29 | 32 | 38 | 45 | 51 | 58 | 64 | 70 | 77 | 83 | 89 | 96 | 102 | 109 | 115 | 121 | 128 | |
| 240 | 3.3 | 6.7 | 10.0 | 13.3 | 16.7 | 20 | 23 | 27 | 30 | 33 | 40 | 47 | 53 | 60 | 67 | 73 | 80 | 87 | 93 | 100 | 107 | 113 | 120 | 127 | 133 | |
| 250 | 3.5 | 6.9 | 10.4 | 13.9 | 17.4 | 21 | 24 | 28 | 31 | 35 | 42 | 49 | 56 | 63 | 69 | 76 | 83 | 90 | 97 | 104 | 111 | 118 | 125 | 132 | 139 | |
| 260 | 3.6 | 7.2 | 10.8 | 14.4 | 18 | 22 | 25 | 29 | 33 | 36 | 43 | 51 | 58 | 65 | 72 | 79 | 87 | 94 | 101 | 108 | 116 | 123 | 130 | 137 | 144 | |
| 270 | 3.8 | 7.5 | 11.3 | 15.0 | 19 | 23 | 26 | 30 | 34 | 38 | 45 | 53 | 60 | 68 | 75 | 83 | 90 | 98 | 105 | 113 | 120 | 128 | 135 | 143 | 150 | |
| 280 | 3.9 | 7.8 | 11.7 | 15.6 | 19 | 23 | 27 | 31 | 35 | 39 | 47 | 54 | 62 | 70 | 78 | 86 | 93 | 101 | 109 | 117 | 124 | 132 | 140 | 148 | 156 | |
| 290 | 4.0 | 8.1 | 12.1 | 16.1 | 20 | 24 | 28 | 32 | 36 | 40 | 48 | 56 | 64 | 73 | 81 | 89 | 97 | 105 | 113 | 121 | 129 | 137 | 145 | 153 | 161 | |
| 300 | 4.2 | 8.3 | 12.5 | 16.7 | 21 | 25 | 29 | 33 | 38 | 42 | 50 | 58 | 67 | 75 | 83 | 92 | 100 | 108 | 117 | 125 | 133 | 142 | 150 | 158 | 167 | |
| TABLE A-6 | MAXIMUM ONE-WAY WIRE DISTANCE (FT) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--24-VOLT CIRCUITS-COPPER | ||||||||||||||||
| AMERICAN WIRE GAUGE (AWG) WIRE SIZE | ||||||||||||||||
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 300MCM | 500MCM | ||
| AMPS | WATTS | |||||||||||||||
| 2 | 48 | 55 | 88 | 140 | 222 | 353 | 561 | 709 | 896 | 1125 | 1417 | 1782 | 2258 | 2875 | 4036 | 6792 |
| 4 | 96 | 28 | 44 | 70 | 111 | 176 | 280 | 354 | 448 | 563 | 709 | 891 | 1129 | 1438 | 2018 | 3396 |
| 6 | 144 | 18 | 29 | 47 | 74 | 118 | 187 | 236 | 299 | 375 | 472 | 594 | 753 | 958 | 1345 | 2264 |
| 8 | 192 | 14 | 22 | 35 | 56 | 88 | 140 | 177 | 224 | 281 | 354 | 446 | 565 | 719 | 1009 | 1698 |
| 10 | 240 | 18 | 28 | 44 | 71 | 112 | 142 | 179 | 225 | 283 | 356 | 452 | 575 | 807 | 1358 | |
| 12 | 288 | 15 | 23 | 37 | 59 | 93 | 118 | 149 | 188 | 236 | 297 | 376 | 479 | 673 | 1132 | |
| 14 | 336 | 20 | 32 | 50 | 80 | 101 | 128 | 161 | 202 | 255 | 323 | 411 | 577 | 970 | ||
| 16 | 384 | 17 | 28 | 44 | 70 | 89 | 112 | 141 | 177 | 223 | 282 | 359 | 504 | 849 | ||
| 18 | 432 | 16 | 25 | 39 | 62 | 79 | 100 | 125 | 157 | 198 | 251 | 319 | 448 | 755 | ||
| 20 | 480 | 14 | 22 | 35 | 56 | 71 | 90 | 113 | 142 | 178 | 226 | 288 | 404 | 679 | ||
| 25 | 600 | 18 | 28 | 45 | 57 | 72 | 90 | 113 | 143 | 181 | 230 | 323 | 543 | |||
| 30 | 720 | 15 | 24 | 37 | 47 | 60 | 75 | 94 | 119 | 151 | 192 | 269 | 453 | |||
| 35 | 840 | 20 | 32 | 40 | 51 | 64 | 81 | 102 | 129 | 164 | 231 | 388 | ||||
| 40 | 960 | 18 | 28 | 35 | 45 | 56 | 71 | 89 | 113 | 144 | 202 | 340 | ||||
| 45 | 1080 | 16 | 25 | 31 | 40 | 50 | 63 | 79 | 100 | 128 | 179 | 302 | ||||
| 50 | 1200 | 14 | 22 | 28 | 36 | 45 | 57 | 71 | 90 | 115 | 161 | 272 | ||||
| 60 | 1440 | 19 | 24 | 30 | 38 | 47 | 59 | 75 | 96 | 135 | 226 | |||||
| 70 | 1680 | 16 | 20 | 26 | 32 | 40 | 51 | 65 | 82 | 115 | 194 | |||||
| 80 | 1920 | 14 | 18 | 22 | 28 | 35 | 45 | 56 | 72 | 101 | 170 | |||||
| 90 | 2160 | 16 | 20 | 25 | 31 | 40 | 50 | 64 | 90 | 151 | ||||||
| 100 | 2400 | 14 | 18 | 23 | 28 | 36 | 45 | 58 | 81 | 136 | ||||||
| 110 | 2640 | 16 | 20 | 26 | 32 | 41 | 52 | 73 | 123 | |||||||
| 120 | 2880 | 15 | 19 | 24 | 30 | 38 | 48 | 67 | 113 | |||||||
| 130 | 3120 | 14 | 17 | 22 | 27 | 35 | 44 | 62 | 104 | |||||||
| 140 | 3360 | 16 | 20 | 25 | 32 | 41 | 58 | 97 | ||||||||
| 150 | 3600 | 15 | 19 | 24 | 30 | 38 | 54 | 91 | ||||||||
| 160 | 3840 | 14 | 18 | 22 | 28 | 36 | 50 | 85 | ||||||||
| 170 | 4080 | 17 | 21 | 27 | 34 | 47 | 80 | |||||||||
| 180 | 4320 | 16 | 20 | 25 | 32 | 45 | 75 | |||||||||
| 190 | 4560 | 15 | 19 | 24 | 30 | 42 | 71 | |||||||||
| 200 | 4800 | 14 | 18 | 23 | 29 | 40 | 68 | |||||||||
| TABLE A-7 | MAXIMUM ONE-WAY WIRE DISTANCE (FT) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--48-VOLT CIRCUITS-COPPER | ||||||||||||||||
| AMERICAN WIRE GAUGE (AWG) WIRE SIZE | ||||||||||||||||
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 300MCM | 500MCM | ||
| AMPS | WATTS | |||||||||||||||
| 2 | 96 | 110 | 176 | 279 | 445 | 706 | 1121 | 1417 | 1791 | 2250 | 2835 | 3564 | 4517 | 5751 | 8072 | 13585 |
| 4 | 192 | 55 | 88 | 140 | 222 | 353 | 561 | 709 | 896 | 1125 | 1417 | 1782 | 2258 | 2875 | 4036 | 6792 |
| 6 | 288 | 37 | 59 | 93 | 148 | 235 | 374 | 472 | 597 | 750 | 945 | 1188 | 1506 | 1917 | 2691 | 4528 |
| 8 | 384 | 28 | 44 | 70 | 111 | 176 | 280 | 354 | 448 | 563 | 709 | 891 | 1129 | 1438 | 2018 | 3396 |
| 10 | 480 | 22 | 35 | 56 | 89 | 141 | 224 | 283 | 358 | 450 | 567 | 713 | 903 | 1150 | 1614 | 2717 |
| 12 | 576 | 18 | 29 | 47 | 74 | 118 | 187 | 236 | 299 | 375 | 472 | 594 | 753 | 958 | 1345 | 2264 |
| 14 | 672 | 16 | 25 | 40 | 64 | 101 | 160 | 202 | 256 | 321 | 405 | 509 | 645 | 822 | 1153 | 1941 |
| 16 | 768 | 22 | 35 | 56 | 88 | 140 | 177 | 224 | 281 | 354 | 446 | 565 | 719 | 1009 | 1698 | |
| 18 | 864 | 20 | 31 | 49 | 78 | 125 | 157 | 199 | 250 | 315 | 396 | 502 | 639 | 897 | 1509 | |
| 20 | 960 | 18 | 28 | 44 | 71 | 112 | 142 | 179 | 225 | 283 | 356 | 452 | 575 | 807 | 1358 | |
| 25 | 1200 | 22 | 36 | 56 | 90 | 113 | 143 | 180 | 227 | 285 | 361 | 460 | 646 | 1087 | ||
| 30 | 1440 | 19 | 30 | 47 | 75 | 94 | 119 | 150 | 189 | 238 | 301 | 383 | 538 | 906 | ||
| 35 | 1680 | 16 | 25 | 40 | 64 | 81 | 102 | 129 | 162 | 204 | 258 | 329 | 461 | 776 | ||
| 40 | 1920 | 22 | 35 | 56 | 71 | 90 | 113 | 142 | 178 | 226 | 288 | 404 | 679 | |||
| 45 | 2160 | 20 | 31 | 50 | 63 | 80 | 100 | 126 | 158 | 201 | 256 | 359 | 604 | |||
| 50 | 2400 | 18 | 28 | 45 | 57 | 72 | 90 | 113 | 143 | 181 | 230 | 323 | 543 | |||
| 60 | 2880 | 15 | 24 | 37 | 47 | 60 | 75 | 94 | 119 | 151 | 192 | 269 | 453 | |||
| 70 | 3360 | 20 | 32 | 40 | 51 | 64 | 81 | 102 | 129 | 164 | 231 | 388 | ||||
| 80 | 3840 | 18 | 28 | 35 | 45 | 56 | 71 | 89 | 113 | 144 | 202 | 340 | ||||
| 90 | 4320 | 16 | 25 | 31 | 40 | 50 | 63 | 79 | 100 | 128 | 179 | 302 | ||||
| 100 | 4800 | 22 | 28 | 36 | 45 | 57 | 71 | 90 | 115 | 161 | 272 | |||||
| 110 | 5280 | 20 | 26 | 33 | 41 | 52 | 65 | 82 | 105 | 147 | 247 | |||||
| 120 | 5760 | 19 | 24 | 30 | 38 | 47 | 59 | 75 | 96 | 135 | 226 | |||||
| 130 | 6240 | 17 | 22 | 28 | 35 | 44 | 55 | 69 | 88 | 124 | 209 | |||||
| 140 | 6720 | 16 | 20 | 26 | 32 | 40 | 51 | 65 | 82 | 115 | 194 | |||||
| 150 | 7200 | 15 | 19 | 24 | 30 | 38 | 48 | 60 | 77 | 108 | 181 | |||||
| 160 | 7680 | 18 | 22 | 28 | 35 | 45 | 56 | 72 | 101 | 170 | ||||||
| 170 | 8160 | 17 | 21 | 26 | 33 | 42 | 53 | 68 | 95 | 160 | ||||||
| 180 | 8640 | 16 | 20 | 25 | 31 | 40 | 50 | 64 | 90 | 151 | ||||||
| 190 | 9120 | 15 | 19 | 24 | 30 | 38 | 48 | 61 | 85 | 143 | ||||||
| 200 | 9600 | 18 | 23 | 28 | 36 | 45 | 58 | 81 | 136 | |||||||
| TABLE A-8 | MAXIMUM ONE-WAY WIRE DISTANCE (FT) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--120-VOLT CIRCUITS-COPPER | ||||||||||||||||
| AMERICAN WIRE GAUGE (AWG) WIRE SIZE | ||||||||||||||||
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 300MCM | 500MCM | ||
| AMPS | WATTS | |||||||||||||||
| 2 | 240 | 276 | 439 | 698 | 1112 | 1765 | 2804 | 3543 | 4478 | 5625 | 7087 | 8911 | 11292 | 14377 | 20179 | 33962 |
| 4 | 480 | 138 | 220 | 349 | 556 | 882 | 1402 | 1772 | 2239 | 2813 | 3543 | 4455 | 5646 | 7188 | 10090 | 16981 |
| 6 | 720 | 92 | 146 | 233 | 371 | 588 | 935 | 1181 | 1493 | 1875 | 2362 | 2970 | 3764 | 4792 | 6726 | 11321 |
| 8 | 960 | 69 | 110 | 174 | 278 | 441 | 701 | 886 | 1119 | 1406 | 1772 | 2228 | 2823 | 3594 | 5045 | 8491 |
| 10 | 1200 | 55 | 88 | 140 | 222 | 353 | 561 | 709 | 896 | 1125 | 1417 | 1782 | 2258 | 2875 | 4036 | 6792 |
| 12 | 1440 | 46 | 73 | 116 | 185 | 294 | 467 | 591 | 746 | 938 | 1181 | 1485 | 1882 | 2396 | 3363 | 5660 |
| 14 | 1680 | 39 | 63 | 100 | 159 | 252 | 401 | 506 | 640 | 804 | 1012 | 1273 | 1613 | 2054 | 2883 | 4852 |
| 16 | 1920 | 35 | 55 | 87 | 139 | 221 | 350 | 443 | 560 | 703 | 886 | 1114 | 1412 | 1797 | 2522 | 4245 |
| 18 | 2160 | 31 | 49 | 78 | 124 | 196 | 312 | 394 | 498 | 625 | 787 | 990 | 1255 | 1597 | 2242 | 3774 |
| 20 | 2400 | 28 | 44 | 70 | 111 | 176 | 280 | 354 | 448 | 563 | 709 | 891 | 1129 | 1438 | 2018 | 3396 |
| 25 | 3000 | 22 | 35 | 56 | 89 | 141 | 224 | 283 | 358 | 450 | 567 | 713 | 903 | 1150 | 1614 | 2717 |
| 30 | 3600 | 18 | 29 | 47 | 74 | 118 | 187 | 236 | 299 | 375 | 472 | 594 | 753 | 958 | 1345 | 2264 |
| 35 | 4200 | 16 | 25 | 40 | 64 | 101 | 160 | 202 | 256 | 321 | 405 | 509 | 645 | 822 | 1153 | 1941 |
| 40 | 4800 | 22 | 35 | 56 | 88 | 140 | 177 | 224 | 281 | 354 | 446 | 565 | 719 | 1009 | 1698 | |
| 45 | 5400 | 20 | 31 | 49 | 78 | 125 | 157 | 199 | 250 | 315 | 396 | 502 | 639 | 897 | 1509 | |
| 50 | 6000 | 18 | 28 | 44 | 71 | 112 | 142 | 179 | 225 | 283 | 356 | 452 | 575 | 807 | 1358 | |
| 60 | 7200 | 15 | 23 | 37 | 59 | 93 | 118 | 149 | 188 | 236 | 297 | 376 | 479 | 673 | 1132 | |
| 70 | 8400 | 20 | 32 | 50 | 80 | 101 | 128 | 161 | 202 | 255 | 323 | 411 | 577 | 970 | ||
| 80 | 9600 | 17 | 28 | 44 | 70 | 89 | 112 | 141 | 177 | 223 | 282 | 359 | 504 | 849 | ||
| 90 | 10800 | 16 | 25 | 39 | 62 | 79 | 100 | 125 | 157 | 198 | 251 | 319 | 448 | 755 | ||
| 100 | 12000 | 22 | 35 | 56 | 71 | 90 | 113 | 142 | 178 | 226 | 288 | 404 | 679 | |||
| 110 | 13200 | 20 | 32 | 51 | 64 | 81 | 102 | 129 | 162 | 205 | 261 | 367 | 617 | |||
| 120 | 14400 | 19 | 29 | 47 | 59 | 75 | 94 | 118 | 149 | 188 | 240 | 336 | 566 | |||
| 130 | 15600 | 17 | 27 | 43 | 55 | 69 | 87 | 109 | 137 | 174 | 221 | 310 | 522 | |||
| 140 | 16800 | 16 | 25 | 40 | 51 | 64 | 80 | 101 | 127 | 161 | 205 | 288 | 485 | |||
| 150 | 18000 | 15 | 24 | 37 | 47 | 60 | 75 | 94 | 119 | 151 | 192 | 269 | 453 | |||
| 160 | 19200 | 22 | 35 | 44 | 56 | 70 | 89 | 111 | 141 | 180 | 252 | 425 | ||||
| 170 | 20400 | 21 | 33 | 42 | 53 | 66 | 83 | 105 | 133 | 169 | 237 | 400 | ||||
| 180 | 21600 | 20 | 31 | 39 | 50 | 63 | 79 | 99 | 125 | 160 | 224 | 377 | ||||
| 190 | 22800 | 19 | 30 | 37 | 47 | 59 | 75 | 94 | 119 | 151 | 212 | 357 | ||||
| 200 | 24000 | 18 | 28 | 35 | 45 | 56 | 71 | 89 | 113 | 144 | 202 | 340 | ||||
| TABLE A-9 | MAXIMUM ONE-WAY WIRE DISTANCE (FT) | |||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 3% VOLTAGE DROP--240-VOLT CIRCUITS-COPPER | ||||||||||||||||
| AMERICAN WIRE GAUGE (AWG) WIRE SIZE | ||||||||||||||||
| 14 | 12 | 10 | 8 | 6 | 4 | 3 | 2 | 1 | 1/0 | 2/0 | 3/0 | 4/0 | 300MCM | 500MCM | ||
| AMPS | WATTS | |||||||||||||||
| 2 | 480 | 552 | 878 | 1395 | 2225 | 3529 | 5607 | 7087 | 8955 | 11250 | 14173 | 17822 | 22585 | 28754 | 40359 | 67925 |
| 4 | 960 | 276 | 439 | 698 | 1112 | 1765 | 2804 | 3543 | 4478 | 5625 | 7087 | 8911 | 11292 | 14377 | 20179 | 33962 |
| 6 | 1440 | 184 | 293 | 465 | 742 | 1176 | 1869 | 2362 | 2985 | 3750 | 4724 | 5941 | 7528 | 9585 | 13453 | 22642 |
| 8 | 1920 | 138 | 220 | 349 | 556 | 882 | 1402 | 1772 | 2239 | 2813 | 3543 | 4455 | 5646 | 7188 | 10090 | 16981 |
| 10 | 2400 | 110 | 176 | 279 | 445 | 706 | 1121 | 1417 | 1791 | 2250 | 2835 | 3564 | 4517 | 5751 | 8072 | 13585 |
| 12 | 2880 | 92 | 146 | 233 | 371 | 588 | 935 | 1181 | 1493 | 1875 | 2362 | 2970 | 3764 | 4792 | 6726 | 11321 |
| 14 | 3360 | 79 | 125 | 199 | 318 | 504 | 801 | 1012 | 1279 | 1607 | 2025 | 2546 | 3226 | 4108 | 5766 | 9704 |
| 16 | 3840 | 69 | 110 | 174 | 278 | 441 | 701 | 886 | 1119 | 1406 | 1772 | 2228 | 2823 | 3594 | 5045 | 8491 |
| 18 | 4320 | 61 | 98 | 155 | 247 | 392 | 623 | 787 | 995 | 1250 | 1575 | 1980 | 2509 | 3195 | 4484 | 7547 |
| 20 | 4800 | 55 | 88 | 140 | 222 | 353 | 561 | 709 | 896 | 1125 | 1417 | 1782 | 2258 | 2875 | 4036 | 6792 |
| 25 | 6000 | 44 | 70 | 112 | 178 | 282 | 449 | 567 | 716 | 900 | 1134 | 1426 | 1807 | 2300 | 3229 | 5434 |
| 30 | 7200 | 37 | 59 | 93 | 148 | 235 | 374 | 472 | 597 | 750 | 945 | 1188 | 1506 | 1917 | 2691 | 4528 |
| 35 | 8400 | 32 | 50 | 80 | 127 | 202 | 320 | 405 | 512 | 643 | 810 | 1018 | 1291 | 1643 | 2306 | 3881 |
| 40 | 9600 | 28 | 44 | 70 | 111 | 176 | 280 | 354 | 448 | 563 | 709 | 891 | 1129 | 1438 | 2018 | 3396 |
| 45 | 10800 | 25 | 39 | 62 | 99 | 157 | 249 | 315 | 398 | 500 | 630 | 792 | 1004 | 1278 | 1794 | 3019 |
| 50 | 12000 | 22 | 35 | 56 | 89 | 141 | 224 | 283 | 358 | 450 | 567 | 713 | 903 | 1150 | 1614 | 2717 |
| 60 | 14400 | 18 | 29 | 47 | 74 | 118 | 187 | 236 | 299 | 375 | 472 | 594 | 753 | 958 | 1345 | 2264 |
| 70 | 16800 | 16 | 25 | 40 | 64 | 101 | 160 | 202 | 256 | 321 | 405 | 509 | 645 | 822 | 1153 | 1941 |
| 80 | 19200 | 22 | 35 | 56 | 88 | 140 | 177 | 224 | 281 | 354 | 446 | 565 | 719 | 1009 | 1698 | |
| 90 | 21600 | 20 | 31 | 49 | 78 | 125 | 157 | 199 | 250 | 315 | 396 | 502 | 639 | 897 | 1509 | |
| 100 | 24000 | 18 | 28 | 44 | 71 | 112 | 142 | 179 | 225 | 283 | 356 | 452 | 575 | 807 | 1358 | |
| 110 | 26400 | 16 | 25 | 40 | 64 | 102 | 129 | 163 | 205 | 258 | 324 | 411 | 523 | 734 | 1235 | |
| 120 | 28800 | 15 | 23 | 37 | 59 | 93 | 118 | 149 | 188 | 236 | 297 | 376 | 479 | 673 | 1132 | |
| 130 | 31200 | 21 | 34 | 54 | 86 | 109 | 138 | 173 | 218 | 274 | 347 | 442 | 621 | 1045 | ||
| 140 | 33600 | 20 | 32 | 50 | 80 | 101 | 128 | 161 | 202 | 255 | 323 | 411 | 577 | 970 | ||
| 150 | 36000 | 19 | 30 | 47 | 75 | 94 | 119 | 150 | 189 | 238 | 301 | 383 | 538 | 906 | ||
| 160 | 38400 | 17 | 28 | 44 | 70 | 89 | 112 | 141 | 177 | 223 | 282 | 359 | 504 | 849 | ||
| 170 | 40800 | 16 | 26 | 42 | 66 | 83 | 105 | 132 | 167 | 210 | 266 | 338 | 475 | 799 | ||
| 180 | 43200 | 16 | 25 | 39 | 62 | 79 | 100 | 125 | 157 | 198 | 251 | 319 | 448 | 755 | ||
| 190 | 45600 | 15 | 23 | 37 | 59 | 75 | 94 | 118 | 149 | 188 | 238 | 303 | 425 | 715 | ||
| 200 | 48000 | 22 | 35 | 56 | 71 | 90 | 113 | 142 | 178 | 226 | 288 | 404 | 679 | |||